Chimneys taller than 20’ above the connection will
require a draft test to determine if the draft is too high.
Note: The high burn draft should not exceed .85 IWC.
Some form of a restrictor plate may be required at the
top of high chimneys to reduce the draft. See page 21
for the Draft Test procedure.
Creosote - Formation and Need for Removal - When wood is burned slowly, it produces tar and other organic vapors,
which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney ue
of a slow-burning re. As a result, creosote residue accumulates on the ue lining. When ignited, this creosote makes an
extremely hot re. The pellet vent pipe should be inspected at least twice monthly during the heating season to determine if
a creosote buildup has occurred. If creosote has accumulated it should be removed to reduce the risk of a chimney re.
Guidance on minimizing creosote formation and the need for periodic creosote removal: The chimney should be
inspected during the heating season to determine if a creosote build-up has occurred. If a signicant layer of creosote has
accumulated (3mm or more) it should be removed to reduce the risk of a chimney re.
This boiler may be used and installed into an existing
masonry or Class A metal chimney.
Certain Canadian and Local Codes may require that
the chimney be fully relined.
The venting Can Not be installed in a chimney serv-
ing another appliance.
The chimney should be cleaned and or inspected before
installation of the venting.

NOTE: All installation clearances and restrictions
must be adhered to.
NOTE: Read and follow all of the vent pipe
manufacturers instructions on the proper
installation and support of the vent pipe. Adhere
to all clearances.
DO NOT INSTALL A FLUE DAMPER IN THE
EXHAUST VENTING SYSTEM OF THIS
UNIT.
DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER
APPLIANCE.
INSTALL VENT WALL PASS-THROUGHS AT
CLEARANCES SPECIFIED BY THE VENT
MANUFACTURER
INSTALLATION IS TO BE PERFORMED BY
A QUALIFIED INSTALLER.
NOTE: Use only 4” diameter approved pellet
venting system. Be sure to inspect and clean
exhaust venting system frequently.
KEEP COMBUSTIBLE MATERIALS SUCH
AS GRASS, LEAVES, ETC. AT LEAST 3 FEET
AWAY FROM THE POINT DIRECTLY UNDER
THE VENT TERMINATION. (BETWEEN THE
VENT AND THE GROUND)
WARNING
KEEP COMBUSTIBLES AWAY
FROM FLUE OUTLET.